Active Ethernet I/O Features and Benefits
- 6 DIs supporting PNP, NPN, and Dry contact
- 6 Form A relay output (Normal Open)
- Relay specification: 5A/250 VAC, 5A/30 VDC
- Instant event messaging by TCP/UDP/e-mail/SNMP trap
- DI and Relay counter saving when power off
- PC-based configuration utility and web console
- Power On default relay status setting with sequence
- Easy-to-use Click&GoTM Logic for local output control
- Windows/WinCE VB/VC and Linux C API
- I/O control over Modbus/TCP and SNMP protocol
Introduction
Remote Ethernet Relay ControlThe Moxa ioLogik E2214 is a stand-alone Active Ethernet I/O product with 6 digital inputs and 6 relay outputs. The DIN-Rail mountable Moxa E2214 can be connected to digital switches, alarm lights, buzzers, and warning sirens over Ethernet and IP-based networks. The Moxa ioLogik E2214 also records the built-in relay output usage counter. Even when a sudden power failure is encountered, the Moxa ioLogik E2214 will still be able to record the relay output usage counter in its internal storage before the power is completely shut down.
Make an enquiry for this product
| • LAN: | |
| Ethernet | 10/100Mbps, RJ45 |
| Protection | 1.5KV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for I/O and Network), HTTP, SNTP |
| • Serial: | |
| Interface | RS-485-2w: Data+, Data-, GND |
| Serial Line Protection | 15KV ESD for all signals |
| • Serial Communication Parameters: | |
| Data Bits | 8 |
| Stop Bits | 1 |
| Parity | None |
| Flow Control | None |
| Protocols | Modbus/RTU |
| Speed | 1200 to 115200 bps |
| • Digital Input: | |
| Channels | 6 digital inputs |
| Sensor Type | NPN, PNP, and Dry contact |
| I/O Mode | DI or Event Counter (up to 900 Hz) |
| Dry Contact | Logic 0: short to GND, Logic 1: open |
| Wet Contact | Logic 0: 0 to 3 VDC Logic 1: 10 to 30 VDC |
| Common Type | 6 points/2 COM |
| Isolation | 2K VDC or 3K Vrms |
| Counter Frequency | 900 Hz |
| Digital Filtering Time Interval |
10 ms |
| Over-voltage Protection | 36 VDC |
| Relay Counter Saving | Yes |
| • Digital Output: | |
| Channels | 6 Form A (N.O.) relay outputs, 5A |
| Contact Rating | 5A @ 30 VDC, 5A @ 240 VAC, 5A @ 110 VAC |
| Inductance Load |
2A |
| Resistance Load | 5A |
| Breakdown Voltage | 500 VAC |
| Relay On/Off Time | 10 ms, 5ms (Max.) |
| Initial Insulation Resistance | 1G min. @ 500 VDC |
| Expected Life | 100,000 times (Typical) |
| Initial Contact Resistance | 30m ohms (Max.) |
| Pulse Output | 20 operation times per minutes at rated load |
| Isolation | 3K VDC or 2K Vrms |
| • Physical Characteristics: | |
| Wiring | I/O cable max. 14AWG |
| • Environmental Limits: | |
| Operating Temperature | -10 to 60°C (14 to 140°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| • Power Requirements: | |
| Power Input | 24 VDC nominal, 12 to 48 VDC |
| DO Power | 24 VDC nominal, up to 30 VDC |
| • Agency Approvals: | |
| EMI | FCC Part 15, CISPR (EN55022) class A |
| EMS | IEC 61000-4, IEC 61000-6 |
| Safety | UL508 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| • Warranty: | |
| Warranty Period | 2 years |
| Details | See www.moxa.com/warranty |
Active Ethernet I/O
| Ordering Info | Model No. | Descritpion |
| Click here to order | LCD module with 16 x 2 text display and 5 buttons | |
| Click here to order |
ioLogik E2214 |
Active Ethernet I/O with 6 digital inputs and 6 relay outputs |