Moxa - E2262 Active Ethernet I/O with 8 thermocouple inputs and 4 digital outputs
![]() |
|
|
|
Active Ethernet I/O Features and Benefits
- Front-end intelligence that supports 24 Click&Go™ rules
- Active Messaging with real-time stamp, including SMS, SNMP Trap with I/O status, TCP, and email
- Supports SNMPv1/v2c/v3 protocol
- I/O peer-to-peer function
- Built-in web console
- PC utility: Auto detection of installed modules
- Windows/WinCE VB/VC.NET and Linux C APIs
Introduction
Extending the wiring lengthThe Moxa ioLogik E2262 can extend the wiring length of your sensors up to 10 fold. For example, whereas the wiring for a J-Type may normally extend only 10 m, the Moxa ioLogik E2262 can be used to increase the J-Type TC wiring length up to 100 m.
More accurate temperatesThe Moxa ioLogik E2262 has two sets of cold junction compensation and digital filtering. Calibration, linearization, and calculation are based on the devices traced by the NIST (National Institute of Standards and Technology), and are stored in memory to eliminate this source of error. The Moxa ioLogik E2262 can also detect burnout and disconnection.
Make an enquiry for this product
| • LAN: | |
| Ethernet | 10/100Mbps, RJ45 |
| Protection | 1.5KV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for I/O and Network), HTTP, SNTP |
| • Serial: | |
| Interface | RS-485-2w: Data+, Data-, GND |
| Serial Line Protection | 15KV ESD for all signals |
| • Serial Communication Parameters: | |
| Data Bits | 8 |
| Stop Bits | 1 |
| Parity | None |
| Flow Control | None |
| Protocols | Modbus/RTU |
| Speed | 1200 to 115200 bps |
| • THERMOCOUPLE: |
|
| Effective Resolution | 16-bit |
| Accuracy | +/- 0.1% FSR @ 25˚C, +/- 0.3% FSR @ -10 and 60°C |
| Input Impedence | 1M ohms or better |
| • digital input: |
|
| Channels | 8, thermocouple input |
| Sensor Type | J, K, T, E, R, S, B, N type TC and mV mode |
| Digital Filtering Time Interval | Less than 90ms |
| • Digital Output: | |
| Channels | 4, sink, 36 VDC, 200 mA |
| Pulse Output | 100 Hz |
| Over-voltage Protection | 45 VDC |
| Over-current Limit | 750 mA |
| Over-temperature Shutdown | 175˚C |
| Isolation | 3K VDC or 2K Vrms |
| • Physical Characteristics: | |
| Wiring | I/O cable max. 14AWG |
| • Environmental Limits: | |
| Operating Temperature | -10 to 60°C (14 to 140°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| • Power Requirements: | |
| Input Voltage | 24 VDC nominal, 12 to 48 VDC |
| DO Power | 24 VDC nominal, up to 30 VDC |
| • Agency Approvals: | |
| EMI | FCC Part 15, CISPR (EN55022) class A |
| EMS | IEC 61000-4, IEC 61000-6 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| • Warranty: | |
| Warranty Period | 5 years |
| Ordering Info | Model No. | Descritpion |
| Click here to order |
ioLogik E2262 |
Active Ethernet I/O with 8 thermocouple inputs and 4 digital outputs |
| Click here to order | LCD module with 16 x 2 text display and 5 buttons |